Published on Australian Maritime Safety Authority (https://www.amsa.gov.au)



03/2024 - Testing and inspection of oil filtering equipment approved to meet Resolution MEPC.107(49)

Purpose

This marine notice informs ship operators and recognised organisations of AMSA’s interpretation for the installation and testing of oil filtering equipment (oily water separators) installed on ships.

Oil filtering equipment installed on a ship on or after 1 January 2005 must be approved to meet Resolution MEPC.107(49) to comply with MARPOL Annex I Regulation 14. 

The requirements include;

MEPC. 107(49) Installation arrangement

A diagram outlining MEPC. 107(49) Installation arrangement

AMSA PSC procedure

AMSA port State control officers (PSCOs) will inspect the condition, and operation, of the oily-water separator, filtering equipment and alarm, stopping or monitoring arrangements as described in the Procedures for Port State Control, 2023 Resolution A.1185(33).

Operational testing of oil filtering equipment will require the equipment to be configured to circulate liquid from bilge tank to bilge tank (recirculating facility) and provide an effluent sample to the 15ppm bilge alarm – simulating the discharge of 15ppm bilge separator effluent overboard. When a simulation of effluent sample greater than 15ppm is applied, the PSCO will confirm that the alarm is activated, and that the automatic stopping device (3-way valve) stops effluent discharge overboard. This indicates compliant operation of the system.

The PSCO will confirm that there is a flow of effluent sample from the 15ppm bilge separator that is truly representative, with adequate pressure and flow, to the 15ppm bilge alarm while effluent is being simulated to flow overboard.

In cases where the flow of effluent sample is not a representative sample, including blockage of the sample line or incorrect operation of valves, it is expected that, in accordance with MEPC.107(49) requirements, the fail-safe arrangement will activate the automatic stopping device (3-way valve) and stop effluent discharge overboard.

AMSA’s interpretation is that the failure of the 15ppm bilge alarm to activate the automatic stopping device in the absence of a representative sample of the effluent, represents non- compliance with Resolution MEPC.107(49). That is there is no fail-safe arrangement required by technical specification 4.1.3.

a photo showing a sample line found blocked when no flow observed from 15ppm bilge alarm outlet Figure 2 a photo showing a sample line found blocked when no flow observed from 15ppm bilge alarm outlet Figure 3

Figures 2 and 3 show a sample line found blocked when no flow observed from 15ppm bilge alarm outlet.

AMSA is aware various classification societies advocate for the installation of “flow sensors” in the 15ppm bilge alarm sample line. The flow sensors activate an alarm and operate the automatic stopping arrangements when a truly representative sample, with adequate pressure and flow, is not present at the 15ppm bilge alarm. They also recommend the sealing of all valves installed in the effluent sample pipes so that the valves are locked and sealed in their normal operating position to ensure adequate effluent sampling.

AMSA accepts that MEPC 107(49) does not specifically require the fitting of flow or pressure sensors.

a photo showing a flow sensor and alarm fitted to the 15ppm bilge alarm sample line Fikgure 4 a photo showing a flow sensor and alarm fitted to the 15ppm bilge alarm sample line Figure 5

The above figures 4 and 5 show a flow sensor and alarm fitted to the 15ppm bilge alarm sample line.

A photo showing a sample line valve to 15ppm bilge alarm  sealed open, and signage fitted.     Figure 6
Sample line valve to 15ppm bilge alarm sealed open, and signage fitted.
 A photo showing a sample line valve to 15ppm bilge alarm  sealed open, and signage fitted.     . Figure 7
Verification of flow of sample water from  15ppm bilge alarm.

Considerations during testing

The following sets out AMSA’s considerations when testing oily water separators during port state control inspection with respect to two types of systems approved under MEPC 107(49):

  1. MEPC 107(49) approved system that is fitted with an effluent sample flow sensor to 15ppm bilge alarm.

Operational testing of the equipment is performed by stopping the sample water flow to the 15ppm bilge alarm. If the 15ppm bilge alarm does not alarm when effluent sample flow is stopped for more than 5 seconds, and the automatic stopping device is not activated within 20 seconds, this is considered a failure of the oily discharge monitoring and control system and the 15ppm alarm arrangements. The ship is likely to be detained until the system complies with MARPOL requirements.

  1. MEPC 107(49) approved system that is not fitted with an effluent sample flow sensor to the 15ppm bilge alarm.

The sample water flow through 15ppm bilge alarm should be unobstructed. All valve(s) fitted for sampling line to the 15ppm bilge alarm should be in the normal operating position when testing is performed during port state control inspections. During the test the following will be considered:

Guidelines

MEPC 107(49) – Resolution MEPC 107(49)

Last updated: 7 June 2024